      Lighting load on new construction homes is calculated based on square footage.

      That doesn’t even make sense as it treads someone just putting up a single 5W bulb the same as someone having an indoor hemp plantation or heavy machine shop in their basement.

      • TwiddleTwaddle@lemmy.blahaj.zone
        link
        fedilink
        arrow-up
        3
        ·
        edit-2
        7 hours ago

        Well the NEC still uses wattages from old incandescent bulbs for general lighting load calcs, plus there’s always a reasonable amount of overspeccing built into the calculation.

        You would then add any large loads specifically. Clothes drier, oven, fridge, HVAC, anything that comes with a nameplate wattage rating should be included in the load calc.

        Most utilities these days will also just round up to a 200A service for anything larger than a trailer. Big houses would get multiples of 200A services if needed.